Laserfiche WebLink
Location: Mahee Middle High School Indoor-Air Results <br /> Address: Soo Old Barnstable Road,NSA 'Fable 1 (continued) Date: 11130/2010 <br /> Relative Carbon Carbon Ventilation <br /> Location/ Occupants Temp Tumidity Dioxide Monoxide PM2.5 Window <br /> Roam in Room (IF) (Ppm) inPg/m' enable Supply Exhaust Remarks <br /> 109 26 695 1300 ND 6 Y Y Y UV-off, window open,MT <br /> 110 11 73 30 1516 ND 6 Y Y Y DEM,CPs <br /> A 112 1 69 29 1104 ND 4 N Y Y <br /> 112 A 1 70 30 1097 ISD 4 N Y <br /> 113 1 72 27 911 ND 8 N Y Y PCs, fridge,carpet <br /> 119 0 70 31 654 ND <br /> 120 5 73 32 815 ND 14 Y Y I <br /> 120 A Air cleaner not operating, <br /> Wood Shop 10 76 32 857 ND 30-37 Y Y breach in local exhaust for <br /> food cuttin ui ent <br /> ppm parts per million DO door open .PF personal fan <br /> g I 3=micrograms per cubic meter CP cleaning products CT=ceiling the <br /> D—note detect VIED=water-damaged A1IMT=ajar ceiling tileimi sing ceiling the <br /> P T photo copier UV=univent DEM=dry erase materials <br /> AD=air deodorizer GW—gypsum wallboard <br /> i <br /> Comfort Guidelines <br /> Carbon Dioxide: <600 ppm preferred Temperature: 70-7 'F <br /> 600-800 ppm=acceptable Relative Humidity: 40-60% <br /> 800 uni--indicative of ventilation roblems Particle matter 2.5 <35 Ug/M3 <br /> Table 1, page 2 <br />