Location: Mushpee Middle High School Indoor Air Results <br /> Address; 500 Old Barnstable Road, SIA Table 1 (continued) Date: 11/30/2010 <br /> Relative Carbon Carbon Ventilation <br /> Location/ Occupants Temp humidity Dioxide Monoxide M2. Windows <br /> �Room in Room F % <br /> Remarks <br /> Kiln vented-duct not attached, <br /> Kiln Room 2 70 2 ISD 1 ISI 1'F <br /> PF, 1 �',CP, <br /> 117 Music 10 71 1 1D I Y accumulated sterns <br /> E 107 2 69 31 502 ISD 4 Y Y Y PF,space sink countertop <br /> E 110 2 70 29 493 ND 3 Y Y <br /> E 115 Nurse l 74 26 561 ND 2 N Y Y 2 SVD CT <br /> Cafeteria —200 70 31 699 SID 4 N Y Y <br /> Auditorium fl 70 26 450 ND 5 N Y <br /> Gymnasium 6 69 31 682 ND 6 N Y Y <br /> rt <br /> ppm parts per million D T door opera PF=personal fan <br /> Ag/n,3=micrograms per cubic mete- CP=cleaning products CT=ceiling the <br /> ND=non detect VSD=water-damaged ATAT=ajar ceiling the/missing ceiling the <br /> PC=photo copier U =univent DEM z--dry erase materials <br /> D=air deodorizer GW gypsum wallboard , <br /> Coni fort Guidelines <br /> Carbon Dioxide: <600 ppm preferred Temperature: 70-7 'F <br /> 600-800 ppm=acceptable Relative Humidity: 40- 0% <br /> 800 ppin=indicative of ventilation Problems Particle matter 2.5 <35 ug/Ing <br /> Table 1,page <br />