Laserfiche WebLink
Location: Mushpee Middle iglu School Indoor Air Results <br /> Address: 500 (old Barnstable Road,NIA Table 1 (continued) Date; 11/3012010 <br /> Relative Carbon Carbon Ventilation <br /> Location/ Occupants Temp Humidity Dioxide Monoxide PM2_5 Windows <br /> Room in doom °o pM3 nabs Supply xhaut Remarks <br /> 214 3 73 27 646 ND 3 Y Y Y 6 WD CT,DD <br /> 215 1 72 27 713 ND 3 N Y Y Exhaust vent-dusty, 5 VIED CT, <br /> D <br /> 230 23 74 30 924 ND 4 Y Y Y 4 WD CTs rear exhaust vent <br /> 223 22 72 31 952 STD 7 Y Y Y 4 VSD CT, WD-GW/paint-dry <br /> Accumulated items,3 ISD CT, <br /> 229 17 71 28 585 ND 4 Y Y Y aquarium-green with algal <br /> growth <br /> 234 0 69 28 457 ND 4 Y Y Y 1 VOID CT,plants <br /> .A 235 0 71 28 524 ND 5 N Y Y <br /> 238 1 70 27 550 ND 4 N Y Y <br /> - i <br /> ppni=parts per million D =door open PF 4 personal fan <br /> pglm =micrograms per cubic meter CPT cleaning products CT=ceiling tilt � <br /> ND=non detect VIED=water-damaged AT/M.T=ajar ceiling the/missing ceiling tilt <br /> i <br /> PC'_photo copier U =univ nt DENT dry erase materials <br /> D=air deodorizer GW =gypsum wallboard <br /> Comfort Guidelines <br /> i <br /> Carbon Dioxide: <600 ppm=preferred Temperature: 70-7 'F <br /> 600-800 ppm�acceptable Relative Humidity: 40- 0% <br /> m=indicative of ventilation problems Particle matter 2.5 <35 ugm' <br /> Table 1, page <br />