Laserfiche WebLink
i <br /> Preliminary Inspection 1term <br /> Page 2 <br /> 15. Exectutive Secretary's balcony handrail does not meet the code requirement height <br /> of 42 inches, <br /> 16. There are no fire dampers its the ductwork for the 6 hoar rated vault. The architect <br /> is to verify in writftig the fire rating for the vault. <br /> 17. Rooms without glass in the door such as the Selectmen's office, the ecl l t ent <br /> room off the Executive's office and the electrical room are required to have emergency <br /> lighting. <br /> 18. Required electrical outlets are m s hig on the p1mis and not installed. One per wall <br /> is the required. <br /> 19. There is no exterior light shown on the pians at stair one exit or exterior exit for <br /> basement storage. <br /> i 20. The fire separation at the mwn lobby is not complete. <br />