Laserfiche WebLink
Mr. Dunn also asked to see the numbers for usage amount on a yearly basis. <br /> Anastasia said they will put a table together of estimated weights so we can further <br /> discuss. <br /> Bulk chemicals in containment? <br /> Yes they are contained, will be filled using fill lines. <br /> M-300 — Valve vault— access the gate valves from above ground rather than <br /> having to enter the vault. <br /> Design intent is to minimize water intrusion into the vault, and install one hatch. You <br /> should be able to reach in from the top and not have to enter the contained space. <br /> Is there a manlift that is going to be provided? <br /> Yes, the design is to incorporate DAVIT cranes in order to comply with OSHA. There will <br /> be at least a base near every confined space, it would be a limited number of cranes to <br /> be used on the bases. They will probably be stored in the process building. <br /> Stay away from Proprietary equipment (if at all possible) <br /> We're in the middle of compiling a letter of our recommendations. <br /> Include a RPZ repair kit. <br /> RPZ is a reduced pressure zone valve. <br /> Include flushing pumps for piping (like Chatham) <br /> This will be considered in the next phase of the design. <br /> Include spare conduits <br /> Spares are included in the design. <br /> Require sewer tape & tracer wire <br /> No comments. <br /> Consider hiring an outside vendor for sewer cleaning needs rather than capital <br /> Would the contractor that runs the facility have to flush the lines? It's recommended, if in <br /> the budget, to hire an outside company to flush the lines. <br /> Include Computerized Maintenance program/software for PM & CM needs <br /> (Preventative and Computer Maintenance) Basically it's a management plan to keep track <br /> of what needs to be replaced. The first step is to coordinate with the Town (DEP & IT) <br /> what types of programs are being used to see if we can intubate with those systems. <br /> Where is the station's intrusion alarms going to? SCADA? Dial up? Central <br /> monitoring station? <br /> That's also part of the conversation with DEP & IT. This comment is specifically for <br /> security. <br /> Will the manholes that LPS discharge into be epoxied? <br /> Yes, it's a coating on the inside of the manholes to prevent corrosion. <br /> Will the LPS system have flushing stations? <br /> We put as much gravity as possible in this system, so we won't need this. <br /> The supplemental Carbon Tanks are located inside the building, what product <br /> is planned for this use? MBK <br /> No comment. <br /> I did not see chemical containment alarms on these plans. MBK <br /> There are 3 separate alarms, for the different types of chemicals. <br /> The scum lines at the WRRF are shown to discharge to sludge tanks. Consider <br /> discharge to influent option to help reduce sludge production. MBK <br /> Our proposal is to put the scum in tanks to be hauled away, versus adding it back to the <br /> system. <br /> What is to be provided for in house laboratory testing equipment and where is <br /> this testing to be performed? MBK <br />